Which edition, which section
The 2024 International Residential Code renumbered the stair and guard sections. Stairways moved from R311.7 to R318.7, and guards moved from R312.1 to R321.1. The dimensional limits discussed here did not change between the 2021 and 2024 editions, but the section numbers on a plan review comment will depend on which edition your jurisdiction has adopted, and many still enforce 2021. KerfPlot cites both, written as “2024 IRC R318.7.5.1 [2021: R311.7.5.1]”. Local amendments can tighten any of these numbers, so the building department has the final word.
| Item | Limit | 2024 section | 2021 section |
|---|---|---|---|
| Riser height | ≤ 7-3/4" | R318.7.5.1 | R311.7.5.1 |
| Tread depth (nosing to nosing) | ≥ 10" | R318.7.5.2 | R311.7.5.2 |
| Riser or tread variation in a flight | ≤ 3/8" | R318.7.5.1 / .2 | R311.7.5.1 / .2 |
| Nosing projection (treads < 11") | 3/4" to 1-1/4" | R318.7.5.3 | R311.7.5.3 |
| Headroom | ≥ 6'-8" (80") | R318.7.2 | R311.7.2 |
| Clear width above handrail height | ≥ 36" | R318.7.1 | R311.7.1 |
| Rise of one flight | ≤ 151" | R318.7.3 | R311.7.3 |
| Handrail height above nosing line | 34" to 38" | R318.7.8.1 | R311.7.8.1 |
Riser height is measured vertically between the leading edges of adjacent treads. Tread depth is measured horizontally between the vertical planes of the foremost projection of adjacent treads, so the nosing does not count toward the 10". Headroom is measured vertically from a sloped plane through the tread nosings.
Dividing the total rise
Everything starts with the total rise: the vertical distance from the finished surface at the bottom to the finished floor at the top. Measure it at the actual landing point with a level and a straightedge, because floors are rarely flat over the run of a stair. Divide by the maximum riser and round up to get the number of risers, then divide again to get the actual riser height.
- Riser count
- n = ⌈total rise / 7.75"⌉
- Unit rise
- R = total rise / n
- Treads
- treads = n − 1 (top floor is the last step)
- Total run
- run = treads × T
- Comfort check
- 2R + T ≈ 24" to 25"
| Step | Value |
|---|---|
| Riser count | ⌈105 / 7.75⌉ = ⌈13.55⌉ = 14 |
| Unit rise | 105 / 14 = 7.500" (7-1/2") |
| Treads | 13 |
| Total run | 13 × 10" = 130" |
| Comfort | 2 × 7.5 + 10 = 25" |
| Diagonal of the layout | √(105² + 130²) = 167.1" — a 16' 2×12 stringer |
Thirteen risers would give 8.08", which fails R318.7.5.1, so fourteen is the minimum. Using fifteen is legal and gives a gentler 7.0" rise, at the cost of another 10" of run and a longer stringer.
The bottom-step tread drop
A stringer is laid out with identical rise and run notches from top to bottom. Treads are then added on top of every notch, which raises every step by the tread thickness t. At the top, that is exactly what is needed. At the bottom, the first step now stands R + t above the floor, the single most common stair failure on inspection.
The fix is to cut t off the bottom of the stringer, parallel to the floor line. With 1" thick treads and a 7-1/2" unit rise, the first notch on the stringer is 6-1/2" above its bottom cut, and the finished first step is 7-1/2". If the stringer bears on a subfloor that will later receive finish flooring of thickness f, the drop becomes t − f, because the floor will rise to meet the first tread.
| Tread | Floor at stringer foot | Drop | First notch height |
|---|---|---|---|
| 1" (5/4 deck board) | Finished concrete pad | 1" | 6-1/2" |
| 1-1/16" oak tread | Subfloor; 3/4" hardwood to come | 5/16" | 7-3/16" |
| 1-1/2" (2× tread) | Finished concrete pad | 1-1/2" | 6" |
Throat depth: the AWC DCA 6 5" rule
Cutting notches removes the top of the stringer. What remains between the inside corner of each notch and the bottom edge is the throat, and it is the part that actually carries the load. The American Wood Council’s Prescriptive Residential Wood Deck Construction Guide (DCA 6) calls for at least 5" of throat on cut stringers. KerfPlot passes 5" or more, warns between 3-1/2" and 5", and fails below 3-1/2".
- Notch depth (square to the edge)
- h = R · T / √(R² + T²)
- Throat
- throat = D − h
| Stock | Rise × run | Notch depth h | Throat | DCA 6 |
|---|---|---|---|---|
| 2×12 (11-1/4") | 7-1/2" × 10" | 6.000" | 5.250" | Pass |
| 2×12 (11-1/4") | 7-3/4" × 10" | 6.126" | 5.124" | Pass |
| 2×12 (11-1/4") | 7" × 11" | 5.906" | 5.344" | Pass |
| 2×10 (9-1/4") | 7-1/2" × 10" | 6.000" | 3.250" | Fail |
| 2×10 (9-1/4") | 7" × 11" | 5.906" | 3.344" | Fail |
That is why cut stringers are 2×12 in practice: a 2×10 cannot keep 5" of throat at any comfortable step. Use the actual depth of the lumber, not the nominal; see the nominal-to-actual chart for the dressed sizes.
Guards: when they are required and the sphere rules
Under 2024 IRC R321.1.1 [2021: R312.1.1], a guard is required on open sides of walking surfaces, stairs, ramps and landings that are more than 30" above the floor or grade below at any point within 36" horizontally of the edge. Guards on landings and decks are at least 36" high; on the open sides of stairs the guard is at least 34", measured vertically from the line through the tread nosings (R321.1.2).
| Location | Sphere that must not pass | Provision |
|---|---|---|
| Guard infill on decks, landings, balconies | 4" | R321.1.3 |
| Guards on the open sides of stairs | 4-3/8" | Exception 2 |
| Triangle formed by riser, tread and bottom rail | 6" | Exception 1 |
To space balusters, solve for the number of pieces that keeps the gap under the sphere, then distribute the leftover evenly. Between posts with 72" of clear run and 1-1/2" square balusters on a level deck guard:
- Minimum pieces
- n ≥ (L − g_max) / (w + g_max) = (72 − 4) / 5.5 = 12.36 → 13
- Equal gap
- g = (L − n · w) / (n + 1) = (72 − 19.5) / 14 = 3.75"
Plan for the gap to stay below the limit after the wood moves; a 3-3/4" gap gives 1/4" of margin. On the open side of a stair with 10" treads, two 1-1/2" balusters per tread leave 3-1/2" gaps, inside the 4-3/8" stair allowance. Open risers more than 30" above the floor must also stop a 4" sphere (R318.7.5.1).